6,12, or 24 Volt, High Wattage Emergency Light
6,12, or 24 Volt, High Wattage Emergency Light
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. Do not use outdoors.
2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Use caution when handling batteries. Avoid possible shorting.
5. Equipment should be mounted in locations and at heights where it will
not readily be subjected to tampering by unauthorized personnel.
6. The use of accessory equipment not recommended by the manufac-
turer may cause an unsafe condition.
7. Caution: If optional Halogen cycle lamp(s), symbol (H—), are used in
this equipment, to avoid shattering: do not operate lamp in excess of
rated voltage, protect lamp against abrasion and scratches and
against liquids when lamp is operating, dispose of lamp with care.
8. Halogen cycle lamps operate at high temperatures. Do not store or
place flammable materials near lamp.
9. Do not use this equipment for other than intended use.
10. All servicing should be performed by qualified service personnel.
SAVE THESE INSTRUCTIONS
Installation
1. TURN OFF AC POWER.
2. Route AC circuit wires to electrical box and leave 12’’ of wire length.
3. Securely mount unit in place. Connect AC supply wiring to unit as fol-
lows:
For 120 VAC operation : — Black to 120 VAC, White to neutral *
For 277 VAC operation : — Orange to 277 VAC, White to neutral *
* NOTE : BE SURE TO INSULATE UNUSED WIRE.
4. Extend DC wiring for remote fixtures, (if required), to unit. Wiring must
comply with NEC articles 700 and 720. Do not exceed rated wattage of
unit.
5. When ready to energize AC, plug polarized battery connector into cir-
cuit board. Lamps will not light at this time.
6. Energize AC. Pilot lamp and high charge LED will illuminate.
Testing
(See separate booklet for units with AD option)
Allow one minute for unit to stabilize before testing. To test, depress test
switch. Pilot lights will go out and emergency lamps will come on. When
test switch is release, emergency lamps will go off and both pilot lights will
come on. Allow a minimum of 24 hours charge time after installation or
power failure for initial full load testing.
Maintenance
Wet Battery:
Periodically inspect fluid levels on all cells. If refilling is required,
use distilled water only, refill to designated upper line.
IMPORTANT NOTE:
If unit is installed in an area of high temperatures, increase peri-
odic inspection intervals, as higher watter usage will result.
(Observe safety precaution when handling corrosive batteries.)
Dry battery:
None required. Unit should be tested monthly in accordance with the
requirements of NFPA 101, Life Safety Code, or local codes.
Important notice
This equipment is furnished with a low battery disconnect circuit in the
emergency mode. If the building is to be unoccupied for an extended
period of time and all the power is to be disconnected, the internal batter-
ies must be unplugged from the circuit board to prevent damage. Do not
allow the battery wires to short circuit.
Battery terminals are mounted on the component side of
the circuit board. Make sure to separate lamp load evenly on both circuits.
Battery
Assy.
To
DC
Lamps
“CT”(Center Tap)
used only for
6 volt unites
L1+ L1-
L2+
B+ B-
F1 F2
TR/SEC
CT
TR/SEC
L2-